Address:
,China
Main Products:
Dry Type Transformers,Oil Filled Transformers,Oil immersed transformer,circuit breaker,switchgear,UPS
GCK low voltage withdrawableswitchgear consists of the power center (PC cabinet) and the motor control center (MCC cabinet). It is used in the industrial field such as power plant, petroleum, chemical industry, construction, metallurgy, spinning and weaving and light industry, etc, for power-receiving, feeding, bus connection, lighting, motor control and wattless power compensation.
Working conditions:
Install height: altitude ≤2000m
Ambient temperature:
- Max temperature: +40°C
- Min temperature -5°C
Dimension (H*D*W): 2200mm*1000mm*600mm
Electrical Parameters:
Item | Data |
Rated Insulation Voltage(V) | 660 |
Rated Working voltage(V) | 380 |
Auxiliary Circuit Working Voltage(V) | DC:110/220 |
Rated Frequency(HZ) | 50 |
Rated Current of Horizontal Bus(A) | 1000, 1250, 1600, 2000, 2500, 3200 |
Rated Current of Vertical Bus(A) | 630, 800, 1600 |
Rated Current of Main Circuit Connector(A) | 400, 800 |
Rated Current of Control Circuit Connector(A) | 10 |
Maximum Current of Feeding Circuit(A) | 1600 |
Electric Circuit Current(A) | 1000, 1250, 1600, 2000, 2500, 3200 |
Rated Short-time Withstand Current(kA) | 30,50 |
Rated Peak Withstand Current(kA) | 63,105 |
Drawer Breaking Capacity(kA) | 30-50 |
Protection Class | IP30 |