Address:
,China
Main Products:
Dry Type Transformers,Oil Filled Transformers,Oil immersed transformer,circuit breaker,switchgear,UPS
GGD Low-voltage fixed switchgear is applicable to the distributing systems with an alternating current of 50Hz, a rated working voltage of 380V and a rated working current up to 3150A. Usually this type of switchgear is applied in the power plants, transformer substations and industrial enterprises such as mining or chemical factory. It is used for the purposes of power transformation, distribution and control of power, lighting and distributing equipment.
Working condition:
Install height: altitude ≤2000m
Ambient temperature:
- Max temperature: +40°C
- Min temperature -5°C
Dimension (H*D*W): 2200mm*1000mm*600mm
Electrical Parameters:
Model | Rated Voltage(V) | Rated Current(A) | Rated Short Circuit Breaking Current(KA) | Rated Short-time Withstand Current(KA) | Rated Peak Withstand Current(kA) | |
GGD1 | 380 | A | 1000 | 15 | 15 | 30 |
B | 600 (630) | |||||
C | 400 | |||||
GGD2 | 380 | A | 1500(1600) | 30 | 30 | 63 |
B | 1000 | |||||
C | 630 | |||||
GGD3 | 380 | A | 3150-6300 | 50 | 50 | 105 |
B | 2500 | |||||
C | 2000 |