Address:
,China
Main Products:
Dry Type Transformers,Oil Filled Transformers,Oil immersed transformer,circuit breaker,switchgear,UPS
S15 series amorphous metal core distribution transformers are the best energy-saving distribution transformers at present. They save energy remarkably that their no-load losses are only 1/4~1/5 of S9 series products. S15 series especially suitable for the users of low load rate, such as the rural area and developing region.
Working conditions:
Install height: altitude ≤ 1000m
Ambient temperature:
max temperature: +40°C;
min temperature: -30°C (for indoor transformer)
Electrical Parameters:
Rated Capacity | H.V. | Tapping | L.V. | Connection Symbol | Loss(W) | No-load | Short | Weight(kg) | ||
No load | Full load | Oil | Total Weight | |||||||
30 | 13.2 | ±2×2.5% | 0.4 | Yyno | 33 | 600 | 1.7 | 4 | 130 | 630 |
50 | 43 | 870 | 1.3 | 4 | 160 | 710 | ||||
63 | 50 | 1040 | 1.2 | 4 | 160 | 750 | ||||
80 | 60 | 1250 | 1.1 | 4 | 170 | 810 | ||||
100 | 75 | 1500 | 1 | 4 | 180 | 870 | ||||
125 | 85 | 1800 | 0.9 | 4 | 190 | 940 | ||||
160 | 100 | 2200 | 0.7 | 4 | 210 | 1050 | ||||
200 | 120 | 2600 | 0.7 | 4 | 230 | 1140 | ||||
250 | 140 | 3050 | 0.7 | 4 | 260 | 1290 | ||||
315 | 170 | 3650 | 0.5 | 4 | 280 | 1500 | ||||
400 | 200 | 4300 | 0.5 | 4 | 330 | 1710 | ||||
500 | 240 | 5100 | 0.5 | 4 | 370 | 1960 | ||||
630 | 320 | 6200 | 0.5 | 4.5 | 430 | 2250 | ||||
800 | 380 | 7500 | 0.3 | 4.5 | 480 | 2730 | ||||
1000 | 450 | 10300 | 0.3 | 4.5 | 620 | 3300 | ||||
1250 | 530 | 12000 | 0.2 | 4.5 | 730 | 3560 | ||||
1600 | 630 | 14500 | 0.2 | 4.5 | 860 | 3830 |