Main Products:
Dry Type Transformers,Oil Filled Transformers,Oil immersed transformer,circuit breaker,switchgear,UPS
The single phase pole-mounted distribution transformers are specifically designed for the decentralization distribution network of servicing residential overhead distribution loads of town and countryside. They are also suitable for light and diversified power applications. For the transformer core, two types of materials are available: C.R.G. O core and amorphous metal core.
Standard: IEC、GB、ANSI/IEEE、NEMA
Working conditions:
Install height: altitude ≤1000m
Ambient temperature:
- Max temperature: +40°C
- Min temperature -40°C
Electrical Parameters:
(C.R.G.O core)
Rated Capacity | H.V. | Tapping | L.V. | Loss(W) | Weight(kg) | ||
No load | Full load | Oil | Total Weight | ||||
3 | 33 | ±2×2.5% | 0.12~0.24 | 9 | 45 | 10 | 70 |
5 | 19 | 75 | 15 | 92 | |||
10 | 36 | 120 | 22 | 150 | |||
15 | 50 | 195 | 30 | 210 | |||
25 | 80 | 290 | 45 | 258 | |||
37.5 | 105 | 360 | 50 | 340 | |||
50 | 135 | 500 | 62 | 395 | |||
75 | 190 | 650 | 88 | 480 | |||
100 | 210 | 850 | 94 | 530 | |||
167 | 350 | 1410 | 138 | 680 | |||
250 | 500 | 2000 | 250 | 990 | |||
333 | 650 | 2500 | 300 | 1160 |
(amorphous metal core)
Rated Capacity | H.V. | Tapping | L.V. | Loss(W) | Weight(kg) | ||
No load | Full load | Oil | Total Weight | ||||
3 | 33 | ±2×2.5% | 0.12~0.24 | 8 | 45 | 10 | 60 |
5 | 8 | 75 | 17 | 75 | |||
10 | 12 | 120 | 24 | 100 | |||
15 | 15 | 195 | 26 | 125 | |||
25 | 18 | 290 | 33 | 160 | |||
37.5 | 30 | 360 | 54 | 240 | |||
50 | 32 | 500 | 62 | 295 | |||
75 | 45 | 650 | 78 | 420 | |||
100 | 50 | 850 | 89 | 465 | |||
167 | 65 | 1410 | 140 | 650 | |||
250 | 90 | 2000 | 250 | 950 | |||
333 | 120 | 2500 | 300 | 1200 |